Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Electric Type |
Still deciding? Get samples of US$ 20/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
MCCB China Supplier Bym1-250 3p/4p Moulded Case Circuit Breaker MCCB with IEC60947-2
Standard:
circuit breaker and auxiliaries comply with the following international standard:
1.IEC/EN 60947-1
Low-voltage switchgear and controlgear-part 1: General rules;
2.IEC/EN 60947-2
Low-voltage switchgear and controlgear-part 2: Circuit breakers;
MCCB(Standard use environment for MCCB)
1. Ambient temperature: Within the range of -5ºC--+55ºC(However, when the temperature exceed 40ºC,it should be considered to reduce the capacity to use);
2. Relative humidity: Within the range of 45%--85%;
3. Altitude: 2000m or less(However, if it exceeds 1000m, atmosphere correction through humidity test and withstand voltage test can be considered);
4. Atmosphere where excessive steam, oil steam, smoke, dust, salt and other corrosive materials do not exist;
Classification:
According to the poles: 2-poles, 3-poles
According to the rated current: Fix type
Thermal-Magnetic fixed type Circuit Breakers | ||||
Model | BYM1-250 | |||
Breaking Capacity Code | L | M | H | |
Rated Current of Frame size- Inm (A) | 250A | |||
Rated Current-In(40,50 or 55ºC) (A) | 100,125,140,160,180,200,225,250 63 - 80 - 100 -125 - 160(150)A | |||
Rated İnsulation Voltage -Ui(a.c.) 50-60Hz (V) | 800V | |||
Rated operation Voltage -Ue(a.c.) 50-60Hz (V) | 400/415V | |||
Number of Pole | 3 | 4 | ||
Rated ultimate short Circuit breaking Capacity kA Icu AC400V/50Hz O-CO (KA) | 25 | 35 | 50 | |
Rated service short Circuit breaking Capacity kA Ics AC400V/50Hz O-CO-CO (KA) | 12.5 | 22 | 37.5 | |
Rated short-circuit breaking capacity Icm(peak)/cos ф AC400V/50HZ O-CO (KA) | 41/0.3 | 73.5/0.25 | 110/0.25 | |
Rated impulse withstand Voltage -Uimp (V) | 8000 | |||
Dielectric Propery (V) | 3000 | |||
lonization distance (mm) | ≤50/0 | |||
Endurance | Total Cycles | 8000 | ||
Electrical Life | 1000 | |||
Mechanical Life | 7000 | |||
Over Current trip | Thermal and Magnetic release fix type | √ | ||
Category (EN 14048.2/IEC 60947-2) | Main circuit | A/0 | ||
Auxiliary circuit | AC-15 | |||
Under Voltage Release | √ | |||
Shunt Release | √ | |||
Auxiliary Contact | √ | |||
Alarm Contact | √ | |||
Auxiliary Contact and Alarm Contact | √ | |||
Handle Operation Mechanism | √ | |||
Electrical Operastion Mechanism | √ | |||
Terminal cover | √ | |||
Phase seperator | √ | |||
Extention Handle | - | |||
W (mm) | 3P | 107 | ||
4P | 142 | |||
L (mm) | 3P | 165 | ||
4P | 165 | |||
H (mm) | 3P | 72 | ||
4P | 72 | |||
Weight | Fixed version 3P/4P | 1.2/1.6 | ||
Plug-in version 3P/4P | 1.4/1.8 | |||
Draw out version 3P/4P | - |